The NETR/NETW instruction can read and write the M and V variables of the partner (communication partner). Since the M area has limited space (maximum 32 bytes MB0 to 31), the V variable area (10240 bytes) is commonly used as the buffer for communication. Two buffers are identified in each PLC, one for reception and one for transmission.
Programming only needs to call the subroutine created by NETR/NETW in the master station. Then (the main and slave have to do) is to sort the I and AI input data into the send buffer in the v variable area, and then read the receive buffer. The data in the receive buffer of the partner are the same as the data in the send buffer here. Similarly, the data in the receive buffer can be interpreted by reading the data in the receive buffer.
Setting cpu224xp as a slave does not affect the touch screen plugged into PORT1. The two serial ports are separate from each other and can be used separately as master and slave respectively because they have different interrupt numbers. .
How does the Siemens PLC S7-200 communicate with the computer?
1. Just open the device manager of your computer. After installing the driver under normal conditions, a different serial port will be generated. Please write down the generated serial port, as shown below:
2, open the Siemens programming software, if your 200 series PLC is with CN, please change the software to the Chinese version, and the software version needs to be above V4.0 SP4, the above two conditions are indispensable. If it is not CN, except for these two points.
3. Click on the software and the following window appears.
4, click , the following window appears,
5. After selecting “PC/PPI cable (PPI) ”. Point attributes,
6, this step is extremely important, the port here must choose the cable to install the driver generated serial port, remember! Otherwise it is not possible to communicate. The port can be seen in the device manager.
7. Switch to the “PPI” tab. The default value of “Address” is 0. Do not check the two options for “Network parameters”. Otherwise it is not possible to communicate. The “transmission rate” can be selected according to the actual situation of the PLC.
8, after setting these up. All the way down. Then return to the communication interface, double-click “Refresh” to locate the model of the PLC, you can download the program.
Siemens s7-200, usb-ppi communication steps
Siemens s7-200, usb-ppi communication steps:
1. Install the USB-PPI driver and look at the serial port generated in the device management. Connect the computer with STEP 7 MicroWIN programming software with S7-200PLC and USB/PPI cable.

2. Just open the programming software and set the PC/PG interface and select USB.

3. The computer and PLC are connected to upload/download programs via USB/PPI cable.
Can Mitsubishi Q series plc be connected by opc through programming lines?
All PLCs can exchange data with the host computer in OPC mode.
Mitsubishi Q series plc can be connected by opc through programming lines
How does the computer communicate with Mitsubishi Q series PLC?
Mitsubishi Q series PLC communication parameter settings:
Check digit: odd parity, data bit: 8, stop bit: 1.
Set the communication parameters of the COM port of the computer to the communication parameters of the PLC. Then open the PLC programming software, just click on the connection to PLC.
If it is Q02H series, you can also use the normal USB interface printer line connection programming.
The difference with the A series PLC is: select the transparent mode in the dialog box that appears when connecting the A series PLC.
The Q series does do not seem at all.
Mitsubishi Q series PLC communication line, USB port, what model
Model: USB-QC30R2
Mitsubishi q series plc q01cpu with what communication line programming
QC30R2 or USB-QC30R2
What is the difference between the Mitsubishi PLC programming cable SC and the programming cable USB interface?
Computer side of the SC09 programming cable of Mitsubishi PLC is the RS232 serial 9-hole plug. Computer side of the SC09-USB programming cable of Mitsubishi PLC is a USB plug, and the driver needs to be installed. Both functions are the same
USB-QC30R2, what is the Mitsubishi programming cable used for?
USB-QC30R2 is the PLC programming cable of Mitsubishi Q series, USB port! You can download, upload programs, and monitor online the Q series PLC.
Mitsubishi PLC programming cable FX-USB-AW (USB-RS422) driver
How to make Mitsubishi programming USB cable, need to install driver to work?
How to make Mitsubishi programming USB cable, BSB end 2 pin and D9 pin connector 3 pin, BSB end 3 pin and D9 pin connector 2 pin, BSB end 5 pin and D9 pin connector 5 pin Docking, BSB end 4 feet and BSB end 6 feet shorted, D9 pin connector 6 and D9 pin connector 4. Connected to the line is OK, can be downloaded. No driver installed
Can the Mitsubishi FX3U series PLC download the program using the SC09 data cable?
Absolutely okay.
Both the FX series and the A series PLC can use SC09, not only FX2n, but others.
From FX0S to FX3U, including FX2 and A series (with 25 pins)
In addition, the Q series programming port is 6 pins of RS232, which is completely different from the 8 pin of RS422 of the FX series.